🔥 Case Study – External Façade Investigation

🔥 Case Study – External Façade Investigation

Project Overview

Case Study – External Façade Investigation

(Based on Buildtech External Façade Report – Nov 2025 )

🔍 Situation

Buildtech was instructed to undertake an intrusive façade investigation of a 1930s multi-occupancy residential building approximately 24m in height, to:

  • Identify façade construction and materials
  • Assess combustibility and compliance with current regulations
  • Investigate fire-stopping and compartmentation within the external wall
  • Review workmanship and identify any risks or defects

The building comprises traditional solid masonry construction, with a mix of brickwork and stone façades and later alterations including metal spandrel panels beneath bay windows.

Key risk considerations included:

  • Compliance with ADB B3 and B4 requirements
  • Potential for concealed fire spread
  • Unknown construction details due to building age and historic alterations

🎯 Task

Buildtech’s objective was to provide an evidence-based technical assessment of the façade to:

  • Confirm wall build-up and presence (or absence) of cavities
  • Identify materials and combustibility characteristics
  • Assess fire-stopping provisions at key interfaces, including:
    • Compartment floor junctions
    • Window and door perimeters
    • Vent openings
    • Cladding interfaces
  • Highlight defects, risks, and workmanship issues
  • Provide clear recommendations for remediation (if required)

 

⚙️ Action

A risk-led intrusive investigation strategy was undertaken, including:

🔧 Investigation Methods

  • Endoscopic inspections through 10mm drill penetrations
  • Targeted inspections at 11 key façade locations
  • Assessment of:
    • Masonry build-up
    • Floor slab interfaces
    • Openings (windows, doors, vents)
    • Cladding zones

🧱 Key Findings from Investigation

  1. Primary Wall Construction
  • External walls confirmed as solid masonry construction (no cavity)
  • Typical wall thickness:
    • ~180mm to 285mm brickwork
    • Stone + brick composite construction in some areas
  • Concrete floor slabs found built into the masonry envelope
  1. Combustibility
  • External wall materials identified as non-combustible:
    • Brickwork
    • Stone
    • Steel plate elements
  1. Compartmentation
  • No traditional cavity present → cavity barrier requirements largely not applicable
  • Floor slabs provide inherent compartmentation through solid construction
  1. Openings (Windows / Doors / Vents)
  • Openings formed within solid masonry reveals
  • Aluminium window and door frames installed within deep reveals
  • No evidence of concealed cavities promoting unseen fire spread
  1. Localised Defect Identified
  • Behind metal spandrel panels:
    • 42mm void present between steel plate and slab
    • Void found to be filled with newspaper
    • No cavity barrier observed at this location

✅ Result

The investigation provided a clear and evidence-led understanding of the façade:

✔️ Positive Outcomes
  • Building confirmed as predominantly solid, non-combustible construction
  • No widespread façade cavity risk identified
  • Structural form provides robust inherent fire resistance
  • External wall system does not promote vertical or lateral fire spread in typical areas
⚠️ Key Risk Identified
  • Isolated defect at spandrel panel locations:
    • Presence of combustible material (newspaper) within void
    • Lack of fire-stopping or cavity barrier at this interface

💡 Key Insight

This project highlights a common scenario in legacy masonry buildings:

While primary construction may be inherently robust and non-combustible, localised alterations and secondary elements (such as spandrel panels) can introduce disproportionate fire risks if not properly detailed or fire-stopped.

🏁 Outcome

  • Evidence-led intrusive inspections are critical in older buildings where construction assumptions can be misleading
  • Solid masonry buildings can inherently satisfy fire performance requirements, reducing the need for large-scale remediation
  • Localised defects—not systemic failure—often drive risk
  • Targeted remediation is often more appropriate than wholesale intervention

Project Summary

Case Study – External Façade Investigation (Based on Buildtech External Façade Report – Nov 2025 ) 🔍 Situation Buildtech was instructed to undertake an intrusive façade investigation of a 1930s multi-occupancy residential building approximately 24m in height, to: Identify façade construction and materials Assess combustibility and compliance with current regulations Investigate fire-stopping and compartmentation within the […]